Technical Parameters:
CR2-01, CR2-02 , CR3-03, CR4-01, CR5-01, CR5-02,
CR7-03, CR7-04 (Optional)
DC12V, DC24V
Product size
NPT/BSP 11/4", NPT/BSP 11/2", NPT/BSP 2" (Optional)
Maximum working pressure
1.0MPa
Circulation medium
Fluid, Air
Rated voltage
DC12V, DC24, AC/DC9-35V, AC110-230V(Optional)
Wiring control methods
Working current
≤ 800MA
Open/close time
≤ 15 Sec
Life time
50000 times
Valve Body material
Stainless Steel 304
Actuator material
Engineering Plastics
Sealing material
EPDM & PTFE
Actuator rotation
90°
Max. torque force
10 Nm
Cable Length
0.5m,1.5m (Optional)
Environment temperature
-15℃~50℃
Liquid temperature
2℃~90℃
Manual override
NO
Indicator
Yes
Protection class
IP67
Specifications:
Model
Wiring control
Working voltage
Max. torque
T32-S2-C
CR2 01
10Nm
T32-S2-C
CR2 02
AC/DC9-35V
10Nm
T32-S2-C
CR3 03
DC12V, DC24V
10Nm
T32-S2-C
CR4 01
AC110-230V
10Nm
T32-S2-C
CR5 01
DC12V, DC24V
10Nm
T32-S2-C
CR5 02
AC/DC12-24V
10N.M
T32-S2-C
CR7 03
DC12V, DC24V
10N.M
T32-S2-C
CR7 04
AC110-230V
10N.M
Product Dimenstion :
﹡Exceeding the working voltage is forbidden
CR2 02 Wiring Diagram ( 2 wires control – Spring return in case of the power failure)
·When SW is closed , the valve open. the actuator automatically power off after in place
·When SW is open, the valve closed, the actuator automatically power off after in place
﹡Suitable Working Voltage: AC/DC9-35V
﹡Exceeding the working voltage is forbidden
·RD& GR connect with positive, the BK connect with negative。
·SW CLOSED, the valve OPEN, the actuator automatically power off after in place
·SW OPEN, the valve CLOSED, the actuator automatically power off after in place.
﹡Suitable Working Voltage: AC/DC9-35V/AC110-230V
﹡Exceeding the working voltage is forbidden
CR5 01 Wiring diagram ( with feedback signal)
1RD connect with positive, the BK connect with negative,the valve closed, the actuator automatically power off after in place .
2 BK connect with positive, the RD connect with negative,the valve open, the actuator automatically power off after in place .
3.BL & WT are connect when the valve open fully, YW & WT are connect when the valve closed fully
Suitable Working Voltage::DC12V,DC24V
Exceeding the working voltage is forbidden
CR502 Wiring Diagram ( 5 wires control – Spring return)
·When SW is closed , the valve open. the actuator automatically power off after in place
·When SW is open, the valve closed, the actuator automatically power off after in place BL & WT are connect when the valve open fully, YW & WT are connect when the valve cl osed fully
﹡Suitable Working Voltage: AC/DC9-24V,AC/DC110V-230V,
﹡Exceeding the working voltage is forbidden
CR7 03 Wiring Diagram ( 7 wires control with feedback signal )
·RD& GR connect with positive, the BK connect with negative。
·SW CLOSED, the valve OPEN, the actuator automatically power off after in place
·SW OPEN, the valve CLOSED, the actuator automatically power off after in place.
·BL & GY connect with the valve’s fully open signal wiring
·YW & WT connect with the valve’s fully closed signal wiring.
﹡Suitable Working Voltage: DC12V,DC24V
﹡Exceeding the working voltage is forbidden
CR7 04 Wiring Diagram ( 7 wires control with feedback signal )
·RD & BK are connected to the power, WT & YW are connected to the controlled wiring.
·When the SW is closed , the valve open
·When the SW is open , the valve closed
·BL & GY connect with the valve’s fully open signal wiring
·YW & WT connect with the valve’s fully closed signal wiring.
Suitable Working Voltage::AC/DC110V-230V
Exceeding the working voltage is forbidden
Relative Products: |
© 2015 Taizhou Tonhe Flow Control Co.,Ltd.
electric actuator valve|2 way motorized ball valve|automatic drain valve|timer controlled drain valve |motorized valve| motorized water valve |automatic drainage valve|motor operated valve|3 way motorised valve
Website:http://www.china-tonhe.com/ http://www.tonheflow.com/